Wire Size Calculator

SolversPro Wire Size Calculator is a free electrical engineering tool that computes the required American Wire Gauge (AWG) conductor diameter and circuit voltage drop based on current load, cable length, system voltage, and metal resistivity.

NEC Conductor Ampacity & Cross-Section Reference

Standard NEC 310.16 conductor ratings for copper and aluminum conductors rated at 75°C (THHN/THWN-2):

AWG / kcmil Size Circular Mils (CM) Copper (Cu) 75°C Aluminum (Al) 75°C Typical Standard Circuit
14 AWG 4,110 CM 15 A Not Permitted 15A general lighting and convenience receptacles
12 AWG 6,530 CM 20 A 15 A 20A kitchen/bath small appliance circuits
10 AWG 10,380 CM 30 A 25 A 30A electric water heaters and dryer feeds
8 AWG 16,510 CM 50 A 40 A Electric ranges and central A/C compressors
6 AWG 26,240 CM 65 A 50 A 50A EV fast chargers and subpanel feeders

Frequently Asked Questions

Voltage drop is the decrease of electrical potential along the path of a current flowing in an electrical circuit. The National Electrical Code (NEC) recommends a maximum voltage drop of 3% for branch circuits to ensure equipment operates efficiently.

Different materials have different resistivity (K). Copper is a better conductor (K=12.9) than aluminum (K=21.2), meaning you generally need a thicker aluminum wire to carry the same current over the same distance as copper.

We use the standard industry formula: Circular Mils = (K × I × L × Phase Factor) / Allowable Voltage Drop. The result is then mapped to the next largest standard AWG or kcmil wire size.

Single-phase circuits utilize a phase factor of 2 to account for both out-and-back conductor runs, whereas balanced three-phase calculations utilize the square root of 3 (√3 ≈ 1.732) line-to-line factor.